30A/32A 24-Outlet Outlet-Metered & Switched eco PDU


PE8324
  • Remote power outlet control (on / off, power cycle) by individual outlets and outlet groups
  • Power-On sequencing – users can set the power-on sequence and delay time for each outlet to allow equipment to be powered on in the correct order
  • Supports TCP / IP, UDP, HTTP, HTTPS, SSL, DHCP, ARP, NTP, DNS, Telnet, Auto Sense, Ping, SNMP V1,V2 and V3
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
MSRP: Quote Upon Request

ATEN's NRGence line-up is a new generation of green energy power distribution units (eco PDUs) that optimize the efficiency of data center power usage. The PE8324 eco PDUs are intelligent PDUs that contain 24 AC outlets and are available in various IEC / NEMA socket configurations. These models feature proactive overload protection to automatically power off the last outlet that causes the current overload while allowing users to set shutdown priority.

The eco PDUs provide secure, centralized and intelligent power management (power on, off, and cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, and more), as well as the ability to monitor the center's health environment via sensors.*These PDUs offer remote power control combined with real-time power measurement, allowing users to control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet level, depending on the model, from practically any location via a TCP / IP connection.

The power status of each outlet can be set individually, allowing users to switch each device on / off. The eco PDU also offers comprehensive power analysis reports which can separate departments and locations, providing precise measurements of current, voltage, power and watt-hour in a real-time display. Installation and operation are made fast and easy by simply plugging cables into their appropriate ports, and users get to enjoy the intuitive browser-based configuration and management. The eco PDU firmware is upgradeable over the Net, meaning users can download updates from ATEN's website to ensure that their eco PDU is equipped with the latest functionalities and improvements.

The series also supports the 3rd party V3 SNMP manager software and NRGence eco DC (Energy & DCIM Management Web GUI). The eco DC makes it easy when it comes to the management for multiple devices by allowing users to configure eco PDU setting and monitor the power status of the equipment connected to the PDU through a user friendly interface. Along with its set of features, the PE8324 series has become a convenient, reliable and cost-effective solution to help remotely manage power access for multiple computer installations and allocate power resources with efficiency.

* Note:
1. Sensors are optional accessories. A sensor-enabled installation is required to generate more complete energy-efficient data and charts. The higher the sensor installation density is, the more accurate the data generated will be.
2. eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet access usage.

Package Contents

  • 1 x Power Distribution Unit
  • 1 x mounting kit
  • 1 x user instructions
  • Connections
  • Supports 10 / 100M bit Ethernet interface
  • Supports TCP / IP, UDP, HTTP, HTTPS, SSL, DHCP, ARP, NTP, DNS, Telnet, Auto Sense, Ping, SNMP V1,V2 and V3
  • Supports three-level account / password security, IP / MAC filter, 128 bit SSL, and RADIUS
  • Supports CC2000, eco DC, multiple browsers (IE, Firefox, Chrome, and Safari)
  • Metering
  • PDU and outlet level power metering and monitoring
  • Environment monitoring – supports external temperature / temperature and humidity sensors for rack temperature and humidity monitoring
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
  • Supports door sensor
  • Outlet Switch Control
  • Remote power outlet control (On/Off, Power Cycle) by individual outlets and outlet groups
  • Outlet group support at the PDU level
  • On / Off scheduling for individual outlet and outlet groups. Power management tasks can be scheduled on a daily, weekly, or user-specifi ed time basis
  • Supports multiple power control methods — Wake on LAN, System After AC Back, Kill the Power
  • Power-On sequencing — users can set the power-on sequence and delay time for each outlet to allow equipment to be powered on in the correct order
  • Proactive overload protection (POP) – automatically powers off the last outlet that causes the current overload while allowing users to set shutdown priority
FunctionPE8324APE8324BPE8324GPE8324G2PE8324G3
Electrical
Nominal Input Voltage100 – 120 VAC100 – 240 VAC100 – 240 VAC100 – 240 VAC100 – 240 VAC
Maximum Input Current30A(Max); 24A(UL de-rated)30A Max; 24A (UL de-rated)32A Max32A Max32A Max
Input Frequency50-60 Hz50-60 Hz50-60 Hz50-60 Hz50-60 Hz
Input ConnectionNEMA L5-30PNEMA L6-30PIEC 60309 32AIEC 60309 32AIEC 60309 32A
Input Power3600 VA(Max); 2880 VA(UL de-rated)6240 VA(Max); 4992 VA(UL de-rated)7360 VA(Max)7360 VA(Max)7360 VA(Max)
Outlet TypeTotal: 24 x NEMA 5-15R
Bank1-1: Outlet 1 – 8; 8 x NEMA 5-15R
Bank1-2: Outlet 9 – 16; 8 x NEMA 5-15R
Bank2: Outlet 17 – 24; 8 x NEMA 5-15R
Total: 21 x IEC320 C13 + 3 x IEC320 C19
Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19
Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19
Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19
Total: 21 x IEC320 C13 + 3 x IEC320 C19
Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19
Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19
Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19
Total: 6 x IEC320 C13 + 18 x IEC320 C19
Bank1-1: Outlet 1 – 8; 2 x C13 + 6 x C19
Bank1-2: Outlet 9 – 16; 2 x C13 + 6 x C19
Bank2: Outlet 17 – 24; 2 x C13 + 6 x C19
Total: 18 x IEC320 C13 + 6 x IEC320 C19
Bank1-1: Outlet 1 – 8; 6 x C13 + 2 x C19
Bank1-2: Outlet 9 – 16; 6 x C13 + 2 x C19
Bank2: Outlet 17 – 24; 6 x C13 + 2 x C19
Nominal Output Voltage100 – 120 VAC100 – 240 VAC100 – 240 VAC100 – 240 VAC100 – 240 VAC
Maximum Output Current (Outlet)15A(Max); 12A(UL de-rated)C13: 15A(Max); 12A(UL de-rated)
C19: 20A(Max); 16A(UL de-rated)
C13: 10A(Max)
C19: 16A(Max)
C13: 10A(Max)
C19: 16A(Max)
C13: 10A(Max)
C19: 16A(Max)
Maximum Output Current (Bank)20A(Max); 16A(UL de-rated)20A(Max); 16A(UL de-rated)16A(Max)16A(Max)16A(Max)
Maximum Output Current (Total)30A(Max); 24A(UL de-rated)30A(Max); 24A(UL de-rated)32A(Max)32A(Max)32A(Max)
Breakers2 x 16A UL489 Breaker2 x 16A UL489 Breaker2 x 16A UL489 Breaker2 x 16A UL489 Breaker2 x 16A UL489 Breaker
MeteringOutlet Level Current, Voltage, VA, PF, KWh MonitoringOutlet Level Current, Voltage, VA, PF, KWh MonitoringOutlet Level Current, Voltage, VA, PF, KWh MonitoringOutlet Level Current, Voltage, VA, PF, KWh MonitoringOutlet Level Current, Voltage, VA, PF, KWh Monitoring
Outlet SwitchingYesYesYesYesYes
Environment Sensor Ports44444
Physical Properties
Dimensions (L x W x H)177.50 x 6.60 x 4.40 cm
(69.88 x 2.6 x 1.73 in.)
177.50 x 6.60 x 4.40 cm
(69.88 x 2.6 x 1.73 in.)
177.50 x 6.60 x 4.40 cm
(69.88 x 2.6 x 1.73 in.)
177.50 x 6.60 x 4.40 cm
(69.88 x 2.6 x 1.73 in.)
177.50 x 6.60 x 4.40 cm
(69.88 x 2.6 x 1.73 in.)
Weight6.33 kg ( 13.94 lb )6.33 kg ( 13.94 lb )6.33 kg ( 13.94 lb )6.33 kg ( 13.94 lb )6.33 kg ( 13.94 lb )
Power Cord Length1.6 m1.6 m1.6 m1.6 m1.6 m
Environmental
Temperature (Operating / Storage)0 – 50°C / -20 – 60°C0 – 50°C / -20 – 60°C0 – 40°C / -20 – 60°C0 – 40°C / -20 – 60°C0 – 40°C / -20 – 60°C
Humidity (Operating & Storage)0 – 80% RH, Non-Condensing0 – 80% RH, Non-Condensing0 – 80% RH, Non-Condensing0 – 80% RH, Non-Condensing0 – 80% RH, Non-Condensing
Compliance
EMC VerificationFCC Part 15 Class A, Others by RequestFCC Part 15 Class A, Others by RequestCE, Others by RequestCE, Others by RequestCE, Others by Request
Safety VerificationBy RequestBy RequestCE-LVD, Others by RequestCE-LVD, Others by RequestCE-LVD, Others by Request
NoteFor some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.






Desc.Ver.Release DateFile Name
Firmware Upgradev1.6.1512023-05-19 PE-7-8-9-v1.6.151.zip
Firmware Upgradev1.5.1482022-01-21 pe_7_8_9_v1.5.148.zip
Firmware Upgradev1.5.1462021-03-22 pe_7_8_9_v1.5.146.zip
Firmware Upgradev1.5.1442020-03-02 pe_7_8_9_v1.5.144.zip
Firmware Upgradev1.4.1392020-02-21 pe_7_8_9_v1.4.139.zip
Firmware Upgradev1.4.1372019-11-21 PE_7_8_9_v1.4.137.zip
Firmware Upgradev1.4.1352018-04-10 PE_7_8_9_v1.4.135.zip
Firmware Upgradev1.4.1322016-10-28 pe_7_8_9_v1.4.132.zip
Firmware Upgradev1.3.1252015-09-15 pe_7_8_9_v1.3.125.zip
Firmware Upgradev1.2.1172015-01-19 pe_7_8_9_v1.2.117.zip
Firmware Upgradev1.0.0852014-06-19 pe_7_8_9_v1.0.085.zip
Firmware Upgradev1.0.0722013-08-30 pe_7_8_9_v1.0.072.bin
Firmware Upgradev1.0.0642013-03-08 pe9324_v1.0.064.bin
OSDesc.Ver.Release DateFile Name
MIB File
MIB Filev1.1.1152015-05-05 PE_MIB_File_v1.1.115.zip
Others
MIB Filev1.1.1122014-06-19 pe7_8_9_MIB_File_v1.1.112.zip