20A/16A 16-Outlet Metered-Ready Energy PDU


PE1216
  • Real-time PDU current monitoring * * When used in conjunction with the EC1000 Energy Box
  • Space saving 0U rack mount design
  • IEC or NEMA outlet models
MSRP: Quote Upon Request

• PE1216A: 100~120V; North America, Mexico, Japan, Taiwan
• PE1216B: 200~240V; North America, Mexico, Japan, Taiwan
• PE1216G: International

The PE1216 Energy PDU contains 16 AC outlets and is available in IEC or NEMA socket configurations. The PE1216 Energy PDU features a space-saving 0U design that allows it to be mounted vertically on the outside of a rack, resulting in a more efficient use of space in the server room, while providing 16 AC outlets.

The PE1216 Energy PDU can be integrated into an installation with the EC1000 Energy Box*, allowing you to monitor the real-time current and environmental conditions of the Energy PDU from the front panel of the EC1000 at the rack, or via Web GUI remotely – making your server room efficiently green with ease.

* ATEN EC1000 Energy Box and energy management software – eco DC are available at www..aten.com.

Package Contents

  • 1x PE1216 Energy PDU
  • 1x Power Cord
  • 1x Mounting Kit
  • 1x User Instructions
  • Space saving 0U rack mount design
  • IEC or NEMA outlet models
  • Real-time PDU current monitoring *

    * When used in conjunction with the EC1000 Energy Box
FunctionPE1216APE1216BPE1216G
Electrical
Nominal Input Voltage100 – 120 VAC100 – 240 VAC100 – 240 VAC
Maximum Input Current20A(Max)20A(Max)16A(Max)
Input Frequency50-60 Hz50-60 Hz50-60 Hz
Input ConnectionNEMA 5-20PNEMA 6-20PIEC 60320 C20
Input Power2400 VA(Max)4160 VA(Max)3680 VA(Max)
Outlet TypeTotal: 16 x NEMA 5-15RTotal: 16 x IEC320 C13Total: 16 x IEC320 C13
Nominal Output Voltage100 – 120 VAC100 – 240 VAC100 – 240 VAC
Maximum Output Current (Outlet)15A(Max)15A(Max)10A(Max)
Maximum Output Current (Bank)20A(Max)20A(Max)16A(Max)
Maximum Output Current (Total)20A(Max)20A(Max)16A(Max)
Breakers1 x 20A Non-Fuse Breaker1 x 20A Non-Fuse Breaker1 x 16A Non-Fuse Breaker
MeteringBank Level Current Monitoring (Via EC1000 Energy Box)Bank Level Current Monitoring (Via EC1000 Energy Box)Bank Level Current Monitoring (Via EC1000 Energy Box)
Outlet SwitchingNoneNoneNone
Environment Sensor Ports000
Metering AccuracyCurrent Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H)73.00 x 4.40 x 4.40 cm
(28.74 x 1.73 x 1.73 in.)
73.00 x 4.40 x 4.40 cm
(28.74 x 1.73 x 1.73 in.)
73.00 x 4.40 x 4.40 cm
(28.74 x 1.73 x 1.73 in.)
Weight1.32 kg ( 2.91 lb )1.32 kg ( 2.91 lb )1.32 kg ( 2.91 lb )
Power Cord Length3 m3 m3 m
Environmental
Temperature (Operating / Storage)0–50°C / -20–60°C0–50°C / -20–60°C0–50°C / -20–60°C
Humidity (Operating & Storage)0–80% RH, Non-Condensing0–80% RH, Non-Condensing0–80% RH, Non-Condensing
Compliance
EMC VerificationFCC, Others by RequestFCC, Others by RequestCE, C-Tick, Others by Request
Safety VerificationcTUVus, PSE, Others by RequestcTUVus, PSE, Others by RequestTUV-CB, GOST, Others by Request
NoteFor some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format.