Function | PE2340B | PE2340G |
Electrical |
Nominal Input Voltage | 100 – 240 VAC | 100 – 240 VAC |
Maximum Input Current | 30A(Max) | 32A(Max) |
Input Frequency | 50-60 Hz | 50-60 Hz |
Input Connection | NEMA L6-30P | IEC 60309 32A |
Input Power | 6240 VA(Max) | 7360 VA(Max) |
Outlet Type | Total: 40 x IEC320 C13 Bank1: Outlet 1 – 20; 20 x C13 Bank2: Outlet 21 – 40; 20 x C13 | Total: 40 x IEC320 C13 Bank1: Outlet 1 – 20; 20 x C13 Bank2: Outlet 21 – 40; 20 x C13 |
Nominal Output Voltage | 100 – 240 VAC | 100 – 240 VAC |
Maximum Output Current (Outlet) | 15A(Max) | 10A(Max) |
Maximum Output Current (Bank) | 15A(Max) | 16A(Max) |
Maximum Output Current (Total) | 30A(Max) | 32A(Max) |
Breakers | 2 x 16A UL489 Breaker | 2 x 16A UL489 Breaker |
Metering | Bank Level Current/Voltage Monitoring (Via EC2004 Energy Box) | Bank Level Current/Voltage Monitoring (Via EC2004 Energy Box) |
Outlet Switching | None | None |
Environment Sensor Ports | 0 | 0 |
Metering Accuracy | Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% | Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties |
Dimensions (L x W x H) | 132.5 x 6.6 x 4.4 cm | 132.5 x 6.6 x 4.4 cm |
Weight | 4.65 kg | 4.65 kg |
Power Cord Length | 1.6 m | 1.6 m |
Environmental |
Temperature (Operating / Storage) | 0–50°C / -20–60°C | 0–40°C / -20–60°C |
Humidity (Operating & Storage) | 0–80% RH, Non-Condensing | 0–80% RH, Non-Condensing |
Compliance |
EMC Verification | FCC, Others by Request | CE, Others by Request |
Safety Verification | By Request | CE-LVD, Others by Request |
Note | For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format. |